    Full Product Description





    B-13474:

    ONE (1) INDOOR HOUSED SHALLBETTER CAPACITOR BANK
    13200/7620 VOLT
    9 X 200 KVAR CANS DIVIDED INTO 2 STEPS -
    STEP 1 - 600 KVAR
    STEP 2 - 1200 KVAR
    FUSED
    2 BUSHING
    3 X REACTORS (ON EACH STAGE)
    3 X SURGE ARRESTERS (ON EACH STAGE)
    3 X OIL SWITCHES (ON EACH STAGE)
    KIRK KEY INTERLOCKS ON SECTIONS CONTAINING CAPACITORS AND
    DISCONNECT SWITCH

    STAGE 1:

    JOSLYN VERSAVAC 2 CAPACITOR BANK
    600 KVAR
    15 KV UNGROUNDED
    25 KV SOLIDLY GROUNDED
    200 AMP, 120 VAC
    LIST #3148X0302G1
    WIRING DIAGRAM 3148B0819
    95 KV BIL
    3 X FUSED GE CAPACITORS, 7960, 200 KVAR, 2 BUSHING, SINGLE PHASE, 95 KV
    BIL, 60 HERTZ, MFG. 12/99, FUSING RATING 8.3 KV, 40 AMP, 50 KA
    3 X SHALLBETTER REACTORS RATED 200 AMP, 20 MOCROHENRIES,
    CAT. #SB1-CLR-20-200
    3 X ABB INTERMEDIATE CLASS SURGE ARRESTERS RATED 10 KV, 8.4 MCOV,
    STYLE #ER010AA008A
    1 X ABB BAR TYPE CT RATED 13.8 KV, 25:5 RATIO, 11 KV BIL, 0.3 ACC,
    STYLE 7524A03G05
    600 AMP ABB VERSA-RUPTER FUSED DISCONNECT SWITCH
    13.8 KV CONTINUOUS, 17 KV MAX., 40 KA, CAT. #244-042-507 WITH
    3 X GE EJO-1DD FUSES, 15.5 KV/125 AMP/60 HERTZ
    1 X DOUBLE FUSED ABB PT RATED 13.2/13.2Y - 120, 60 HERTZ

    STAGE 2:

    RELAY & CONTROL SECTION
    2 X CURRENT SENSING RELAYS, 2 X NEUTRAL CURRENT RELAYS 7 CONTROLS FOR
    ALL HEATERS
    1 X GEC ALSTHOM (NOVAR 315 CONTROL) MODEL #N31561205CYBAAA
    JOSLYN VERSAVAC 2 CAP BANK
    RATED 1200 KVAR
    15 KV (UNGROUNDED)
    25 KV (SOLIDLY GROUNDED)
    200 AMP
    120 VAC CONTINUOUS
    LIST #3148X0302G1
    WIRING DIAGRAM 3148B0819
    95 KV BIL
    6 X FUSED GE CAPACITORS, 7960 VOLT, 200 KVAR, 2 BUSHING, SINGLE PHASE,
    95 KV BIL, 60 HERTZ, MFG. 1999, FUSE RATING 8.3 KV, 40 AMP, 50 KA
    3 X SHALLBETTER REACTORS RATED 200 AMPS, 20 MOCROHENRIES,
    CAT. #SBI-CLR-20-200
    3 X ABB INTERMEDIATE CLASS SURGE ARRESTERS RATED 10 KV, 8.4 MCOV,
    STYLE ER010AA008A
    1 X ABB BAR TYPE CT RATED 13.8 KV, 25:5 RATIO, 11 KV BIL, 0.3 ACC
    STYLE 7524A03G05